Shopping security
The Triconex 3721 (Part No. 3721) is a high-reliability Analog Input Module engineered for integration with the Tricon™ Triple Modular Redundancy (TMR) system by Schneider Electric. Designed for mission-critical safety applications, this module provides accurate analog signal acquisition while ensuring fault tolerance and continuous operation. Its architecture guarantees that a single hardware or wiring fault does not compromise process safety or trigger unintended shutdowns.
Triple Modular Redundancy (TMR) Architecture
Three independent processing legs (A, B, C) with 2-out-of-3 voting logic
Electrical isolation between legs to prevent fault propagation
Continuous monitoring for "stuck-at" faults and signal drift
High-Precision Analog Performance
32 differential analog input channels
Input voltage ranges: 0–5 VDC or ±5 VDC with ±6% tolerance
Input current support: 4–20 mA via compatible termination panels
Resolution: Selectable 12-bit or 14-bit
Sampling/Update rate: 10 ms per channel
Accuracy: Better than 0.15% of Full Scale Reading (FSR) from 0°C to 60°C
Common-mode rejection: -85 dB (DC–100 Hz)
Input overrange protection: 150 VDC / 115 VAC continuous
Industrial-Grade Design
Weight: 1.36 kg; Shipping weight: 4 kg
High immunity to EMI and vibration
Certified for SIL 3 applications according to IEC 61508
Hot-swappable module for online maintenance without process interruption
| Feature | Specification |
|---|---|
| Input Channels | 32 Differential, DC-Coupled |
| Input Type | Voltage/Current |
| Input Voltage Range | 0–5 VDC or ±5 VDC |
| Resolution | 12-bit or 14-bit programmable |
| Input Update Rate | 10 ms |
| Accuracy | <0.15% FSR (0–60°C) |
| Common Mode Rejection | -85 dB (DC–100 Hz) |
| Input Protection | 150 VDC / 115 VAC continuous |
| Power Consumption | Low heat dissipation for chassis operation |
| Isolation | ≥1500 VDC field-to-logic |
| Weight | 1.36 kg |
Emergency Shutdown (ESD) Systems
Fire & Gas (F&G) Monitoring
Burner Management Systems (BMS)
Turbomachinery Control (TMC)
Q: Can the module be replaced while the system is running?
A: Yes, the Triconex 3721 supports hot-swapping without interrupting safety functions.
Q: Does the module support both voltage and current inputs?
A: Yes, it supports 0–5 VDC or ±5 VDC and 4–20 mA input signals (with appropriate external termination panels).
Q: Is the module suitable for SIL 3 systems?
A: Yes, it is designed and certified for SIL 3 safety-critical applications.
Q: How is signal accuracy ensured across harsh environments?
A: The module features continuous diagnostics, high common-mode rejection, and triple-leg voting to maintain signal integrity.